PEF-301
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Nominal Phase Voltage, V | 220 |
| Mains frequency, Hz | 45-55 |
| Trip threshold for Umin, V | 160-210 |
| Trip threshold for Umax, V | 230-280 |
| Adjustable reset delay, Ton, sec | 1-600 |
| Return delay range to the priority phase, Tr, (5-200), sec | present |
| Return delay range to the priority phase, Tr, (200 -- ∞), sec | absent |
| Fixed switch (de-energization) delay for Umin, sec | 12 |
| Switch delay to reserve phases, ≤, sec | 0.2 |
| Voltage hysteresis, V | 5-7 |
| Accuracy, V | ±3 |
| Maximum switched current of output contacts, ≥, A | 16 |
| Operating phase voltage, V | 400 |
| Transient withstand, V | 450 |
| Power consumption (under load), ≤, VA | 1.0 |
Life of output contacts:
|
100 000 1 mln. |
Protection degree:
|
IP40 IP20 |
| Operating temperature, °C | -25 - +55 |
| Storage temperature, °C | -45 - +70 |
| Weight, no more than, kg | 0.200 |
| Case dimension, mm | 52*88*65 |
| Mounting 35 mm DIN-rail | |
| Mounting position arbitrary | |
The PEF-301 is a digital microprocessor - based device . User sets trip thresholds of the PEF-30 1 , i. e. the minimum and the maximum voltage thresholds on reaching of which the device trips and de-energizes a load (switches the load to a reserve phase). The PEF-301 is connected to the three-phase four-wire mains through the 1(L1), 3(L2), 5(L3), 6(N) input terminals.
The phase L1 is the priority one, i. e. the load will always be energized from the L1 phase if voltage on this phase is present & within user-preset thresholds. The device performs monitoring of voltage presence & values on each phase and if the voltage value on the L1 goes outside the trip threshold range the PEF-301 effects the high speed (a switch delay ≤ 0.2sec) switching of the load to the phase where voltage value is within trip thresholds. If the voltages on both reserve phases are outside the preset trip voltage thresholds the load will be de-energized.
Switching is performed successively from L1 to L2, from L2 to L3 (the corresponding LED indicator glows).
Switching to the phase with unallowable parameters is not performed.
After the load had been switched to reserve phases the monitoring of voltage presence & voltage value on the priority phase is going on and when the voltage parameters on this phase regenerated the load will be switched to the priority phase after user-preset reset delay Tr (5-200 sec) has expired. If Tr is in "∞" position (the priority is excluded) the return to the priority phase is not performed.
If voltage drops below the minimum trip voltage threshold, the load will be switched (de-energized) after the fixed time delay for starting transient drops ignoring (12 sec) has expired.
If voltage exceeds the maximum trip voltage threshold the load will be switched (de-energized) at once.
If the load had been de-energized from all the three phases because of unallowable voltage level on each phase the PEF-301 goes on voltage monitoring on all phases. When voltage parameters regenerate at least on one phase the load will be energized after the reset delay Ton has expired.
Connection under load ≤ 16A (apply jumper straps between the 8-9 and 10-11 terminals)

Internal blocking for sticking of output built-in relay contacts is provided in the PEF-301. Also the PEF-301 performs the monitoring of the magnetic starter power contact position in external circuit and is blocking the power contacts for their sticking (the 12 terminal is used, see WIRING DIAGRAM ¹2).
Magnetic starters-assisted connection under load > 16A (remove jumper straps between the 8-9 and 10-11 terminals)

K1, K2 , K3 - magnetic starters
NOTE: If the voltage is applied to the 12 terminal the switching is not performed.
The PEF-301produced is ready for service and needs no special pre-starting procedure measures. Due to the application of digital technology all the settings in the PEF-301 are calibrated quite accurate, so one needs no monitoring devices to adjust the settings. Application of the switch according to specifications above and the present certificate, continuous work included, relieves of preventive maintenance during service life.
Before the PEF -301 is plugged - in one needs to set trip threshold values on the front panel by the contact arms of potentiometers :
Trip threshold forUmin: 160 - 210V;
Trip threshold forUmax: 230 280V;
Reset delay after the load had been completely de-energized and then voltage parameters regenerated at least on one phase; also this is the initial load energization delay when voltage is applied to the device,Ton: 1-600 sec;
Return delay to the priority phase,Tr: it's adjusted in the 5 - 200 sec range; in the position "∞" the phase priority is excluded.
For refrigerators, conditioners and other compressor equipment Ton is recommended to set within 3-4 min, for other devices Ton is set according to their operating instructions .
The PEF-301 must be connected subject to the safety regulations. To set settings is recommended in "OFF" state. To set settings alive is permitted following to the safety regulations .
Three green LEDsL1, L2, L3 on the front panel indicate the phase that energizes the load. Thered "fault" LED indicator glows when the load is de-energized from all three phases.
It's recommended: