Protection against Faulty Conditions Caused
by Neutral Phase Loss (Neutral Power Lead Breakage) in 3-Phase Distributor
System of 220/380V
A neutral phase loss. i.e. a neutral lead disconnection
from a transformer substation solidly earthed neutral at an inlet service
feeder switchboard can occur in those cases:
If these cases take place in a 3-phase
balanced system, the load will not be influenced. An illustrative example
is a 3-phase induction motor that needs in operation no neutral, because
a 3-phase induction motor winding is balanced and all phases are equally
loaded. But in a single-phase distributor systems phase loads are never
coinciding that brings about phase voltage imbalance. The more a phase
load difference the more is the imbalance. To equalize the phase voltages
one needs to ground the neutral. Then a circulating current will flow
inducing a forced relative-to-neutral phase equalization.
A summing potential is developed in a common point of that 3-phase system
in case of a neutral phase loss. The summing potential is determined by
each phase load resistance. The neutral drift will cause a big phase imbalance.
The phase voltage applied to the C-phase-powered loads will be considerably
less than 220V while the phase voltage applied to the A&B-phase-powered
loads will be considerably greater than 220V. At the same time the line
voltage will remain unchanged. The most crisis situation will arise when
one of the phases has no load at all (no load is carried). Then the voltage
developed in this phase can be close to the line voltage (380V) while
the voltage developed in the most loaded phase will be close to zero.
If a short-circuit in one of the phases occur when a high voltage is applied
the line voltage of 380V can be applied to the all loads that are other
phase-powered.
For the protection from neutral phase loss consequences we recommend
to use microprocessor-based relay devices that are developed and produced
by NOVATEK-ECLECTRO company. Use the RN-101 and RN-111 voltage relays
in 1-Phase systems: the relays will trip for the minimum or the maximum
voltage settings. Use the RNPP-301 and the RNPP-311 voltage monitors/relays
in 3-Phase systems because the relays will trip for phase imbalance
settings.
Our address:
Of.137, 21 Kondratievsky Prospekt, St-Petersburg, 195197, Russia
Tel: +7 901 300 48 46, +7 812 740 77 38
Fax: +7 812 740 74 55
www.novatek-electro.com
e-mail: novatekspb@mail.ru