Universal Protection For Induction Motors:
Myth Or Reality?
1. Introduction
Electric-to-mechanical energy conversion by dint of electric motors
allows easily and economically to actuate diverse operating mechanisms
such as conveyers, lifting-conveying machines, pumps, fans, compressors,
metal-cutting machine tools, rolling mills, garment equipment and so
on. Due to the construction simplicity, high reliability and the democratic
price squirrel-cage induction motors (IMs) are considered to be universal
electric motors. Over 85% of all electric machines are 3-Phase IMs.
By statistics there are approximately 50 millions of the 3-Phase IMs
that run on 0.4 kW in public production of Russia now. Life expectancy
of IMs without a complete overhaul is usually 15-20 years providing
they are put to their proper operation. A proper IM operation means
an IM operates in conformance with nominal parameters given in the IM
ratings. However, more often that not IMs don't operate at rated duties
because of the poor supply voltage quality and the violations of standard
code such as technological overloads, elevated ambient humidity and
temperature, insulation resistance drop and refrigeration system failures
leading to fault IM conditions. Through the faults up to 10% of all
IMs used go unserviceable every year. For instance, 60% of borehole
electric pump units are broken down more often than once a year. Breakdown
of IMs causes serious faults and big property damage that is associated
with technology process outages, fault-induced consequences elimination,
IMs trouble-shooting and repair of IMs failed. Repair of an electric
machine of up to 1kWt power stands in 5-6 US$. You can evaluate the
cost of more powerful machine repair by yourself. Besides an operation
in abnormal conditions gives rise to increased power consumption from
AC mains and reactive power consumption augmentation. Self-evidently
that application of reliable and effective protection against fault
conditions will considerably reduce a number and frequency of faults,
power consumption and operating expenses as well as extend an IM service
life. But in order to find this protection one has to know not only
how and what his IM must be protected from but also the particularities
of the processes that run in IMs on faults.
2. Fault IM conditions
IM faults. There are two basic types in IM faults: mechanical ones
and electric ones. Deformation or break-down of rotor shaft, slackening
of stator core fixing to frame, slackening of rotor core compression
joint, babbitt fusion in plain bearing, failure of separator, ring or
ball in antifriction bearing, impeller break-down, dust and dirt deposit
in moveable elements and so on are regarded as the mechanical faults
which in most cases are caused by the mains phase imbalance radial vibrations,
the mechanical motor shaft overloads, accessories/components or assembling
reject. Up to 10% of all IM faults will be mechanical ones with 8% of
them caused by the phase imbalance and only 2% of them caused by the
mechanical overload. Since a ratio of the faults induced by reject is
very small we will not consider it in this analysis. The mechanical
fault probability has never been estimated, the main part of mechanical
faults is latent and getting exposed only after appropriate tests or
after IM disassemblies have been carried out. However, AC mains voltage
monitoring and an IM shaft load monitoring in most cases allow to minimize
this probability.
Electric IM faults, in its turn, come in three types:
IM mains faults. Electric energy quality is defined
in accordance with a variety of special standard rates, mainly, with
voltage and frequency distortion, even or odd harmonic factor, negative
and zero voltage sequence factors and so on. Because of supply substation
faults, short-circuits in power distribution systems, switching or lightning
disturbances and phase load distribution irregularity the actual values
of many rates exceed the allowable ones. This is the reason of the IM
fault conditions. By statistics up to 80% of the IM faults are directly
or indirectly induced by AC mains voltage faults.

Analysis of electric energy quality indexes against IM operating conditions
shows, for instance, that AC mains voltage stepping-down causes the
stator current increase which leads to the intensive heating of IM insulation
and its life reduction due to the accelerated insulation ageing and
the insulation disruption. AC mains voltage steeping-up, in its turn,
results in a stator magnetic flux increase, the magnetization current
increase, the core heating (up to steel «fire») and the reactive power
consumption augmentation that decreases a power factor.
Generalized data illustrating how the basic electric energy quality
rates affect IM conditions are given in the Table ¹1.
Table ¹ 1
| Energy quality rates |
Common symbol |
Maximum safe rates |
Energy quality index behavior, changes in IM operation |
| Voltage distortion – see fig.1 |
δU |
+ 10% |
Drop by 10% of Unom |
Exceeding by 10% of Unom |
| A motor torque varies directly as voltage squared |
| A motor torque drops by 19%.Temperature goes up by 7°Á. Start-up
delay increases. Sliding function increases by 27,5%, rotor current
increases by 14%, stator current increases by 10% |
An increased motor torque induces shaft overload, belt transmission
overload, starting impact increase. Starting current increases by
12%, a torque increases by 21%, power factor drops by 5% |
| Phase imbalance in 3-Phase system (see fig.2) |
Negative phase voltage sequence factor |
K2U |
4% |
Unallowable phase voltage imbalance (UPVI)
induces the same processes as voltage distortion does. The UPVI
leads to arising of magnetic fields counter-rotating to the rotor
rotation. Rotary circular magnetic field transforms to elliptic
one which induces bearing and winding radial vibrations and failures.
The UPVI induces the current imbalance and an intensive heating.
Long-run operation at the factor boundaries when load is less than
nominal one reduces service life by 10-15%, when the load is the
nominal one the service life cuts in half. If phase imbalance is
50%, the service life reduces to one-fifth – one-tenth of its standard
value. |
| Zero phase voltage sequence factor |
K0U |
4% |
| Voltage sinusoidal distortion -- see fig. 3 |
Voltage sinusoiddistortion factor |
Ku |
12% |
Affects the winding insulation condition and leads
to their disruption to frame. Total electric energy losses increase.
At Ku =10% the total losses increase by 10-15%. Negative sequence
harmonic amount increases, a power factor decreases. |
| U n-fold harmonic factor |
Ku(n) |
Harmonic ordinal ¹ |
Value % |
Exceeding of allowable factor values
of 2nd , 5th and 8th harmonics leads to a considerable increase
of a negative sequence voltage, the overheating and quick failure,
arising of reverse rotating magnetic fields that induce parasitic
torques degrading a speed-torque characteristics.Exceeding of allowable
triplen harmonic values leads to increase of a zero sequence voltage,
inducing a phase voltage imbalance. When the phase voltage imbalance
is more than 15%, operating and starting torques decrease by 25%,
the reactive power consumption from the mains increases by 3-7%.
Increase of allowable 4th and 7th positive sequence harmonic values
leads to the active rotor resistance increasing and speed-torque
characteristic impair. |
| 2 |
3 |
| 3 |
3.75 |
| 4 |
1.5 |
| 5 |
9 |
| 6 |
0.75 |
| 7 |
7.5 |
| 8 |
0.75 |
| 9 |
1.13 |
| 10 |
0.75 |
It should be noted that there are several mains fault types that occur
very frequently but are not regulated by the Standard code because they
are considered to be extreme cases of IM unbalanced conditions. These
are a phase loss, incorrect phase sequence and phase «coincidence».
Phase loss is usually associated with a service cable conductor breakage,
a burned-out fuse,
a circuit-breaker tripping in one of the lines or a line failure. In
Wye-connection of IM windings two phase voltage divides equally and
makes a half of the line voltage Uphase= Uline/2, a voltage in the third
phase is absent. These conditions lead to the higher mains power consumption
and the stator overheating windings. The rotating field will convert
in the pulsating field, there will be no current in the missing phase,
currents in two other phases will increase by 50%. The IM will not turn
even at no-load conditions. There are some IM types which in case of
a phase loss during IM operation generate a so-called «regeneration»
voltage on the missing phase that is close to mains voltage in phase
and in peak value. Then the IM goes in retardation condition and not
being turned off will burn-out for a few seconds.
A faulty condition associated with phase «coincidence» occurs when a
missing mains phase is short-circuited by IM to the other phase. In
this case the same phase voltage is applied on two phases of the IM
and a voltage that is applied on the third phase remains of a normal
level. A minor peak value imbalance is followed by a considerable phase
imbalance that induces considerable negative sequence voltages that
lead to the IM overheating and failure.
The incorrect phase sequence (B-C-A, C-A-B instead of A-B-C) initiates an
IM reversible condition when the IM rotates into the opposite side which
is often forbidden by technology process conditions because it can lead
not only to the IM fault but also to heavy catastrophic effects.
Continuous AC mains voltage presence & quality monitoring, including
harmonic analysis, RMS or average voltage value calculation before an
IM cut-in, the IM operating condition monitoring and monitoring of phase
voltage parameter changes induced by the IM conditions will often allow
to avoid causes of the fault condition, to prevent the short-circuit
& current overload conditions.
IM current faults.
A voltage at IM terminals and IM winding phase currents are in close
interconnection and any, even minute, mains voltage variations induce
considerable changes in the phase currents (see table ¹.1). In order
to provide an IM effective protection the phase current measurement
should be performed as accurately as possible. According to recent studies,
a long-term IM operation under current overload that exceeds the nominal
current by 5% reduces the IM life tenfold. Since the current curve shows
the distinct sinusoidal distortion, especially at starts, it carries
a great number of higher harmonics which exert a considerable effect
on RMS current value. That’s why a decision about IM operations must
be made on calculated RMS current values because if the decision is
made on average signals or, what even worse, on peak values, false conclusion
about no-current overload condition can be reached.
IM current overload comes in two types: balanced overload and unbalanced
overload.
The balanced current overload is generally associated with the mechanical
overloads on an IM shaft. Their values depend directly on the IM conditions
and heat overloads that will be described below.
The major part of IM current faults is primarily associated with the
abnormal conditions inside IMs that induce the unbalanced current overload.
Let’s examine the basic types of these faults (see table ¹2).
Table ¹ 2. Effect of internal abnormal conditions on IM operation.
| Type of fault |
Current changes |
IM operation behavior |
| One phase is missing in the stator winding |
Wye winding connection |
No current in the missing phase. In two other phases
current makes I =1,5 of Inom |
An IM is booming and not turning even at no-load. Rotating field
becomes the pulsing one. In the operating IM with the load equal
to 1/2 of the nominal load, operating currents increase by 15-20%,
frequency drop is inessential. At considerable loads the IM stops
and if the protection is not ON, the IM will quickly fail. |
| Delta winding connection |
No current in the missing phase. In two other phases current is
considerably more than the nominal one. |
Windings are connected to AC mains by open Delta. The stator winding
currents generate the rotary magnetic field, an IM starts normally
and turns at a normal speed. The mains power consumption is much
more than in the normal condition. The torque is close to the nominal
one, but there is an intensive heating of two operating windings.
Linear current in one of the power leads is v3=1,7 times more than
in two others. |
| Turn-to-turn short circuits in the stator winding phase |
Phase current that is supplied to the faulty phase
becomes many times as large (its value depends on the number of
short circuited turns). |
An IM booms and, operating under load, rotates at the reduced
speed. After a while the IM starts to burn. |
| The stator winding phase-to-phase short circuits |
They induce short circuited currents in windings and
in AC mains that 10-100 times exceed the nominal currents. |
Stator windings run hot quickly and if the protection is not ON,
they overheat and burn. |
All internal IM faults are accompanied by a considerable phase current
unbalance that several times exceeds the voltage imbalance. The constant
current monitoring, therefore, allowing to control current imbalance
– phase imbalance relation provides instant recognition of these faults
and alarms users to cut out the IM fast.
IM conditions.
There are four basic nominal IM conditions that are defined by load
behavior: long-term, short-term, intermittent and mixed cycles. Without
going into details of the cycles mentioned above it should be noted
that a basic under-load operation characteristic is IM thermal response.
An IM operation is always accompanied by its heating caused by processes
that occur in the IM and energy losses. Design IM life is eventually
depending on its allowable insulation heating temperature. Modern IMs
are classified by A, E, B, F, H insulation classes with allowable heating
temperatures as follows: A – 105°C, E– 120°C, B – 130°C, F – 155°C,
H – 180°C, C –over 180°C. Exceeding of allowable temperature causes
premature insulation destruction and considerably reduces an IM life.
However IM operations in service generally differ from the standardized
ones. More common is the quick varying load condition when the IM goes
into overload condition, then returns to the design condition or the
under-nominal-load condition. If the machine is operating in the long-term
condition with varying load (P1, P2, P3…), an unsteady-state heat process
is taking place (see fig. 4), because different power losses and, therefore,
different heat losses arise in it for different time intervals t1, t2,
t3, t4. In order to control effectively the heat quality accumulated
by an IM in the operation one needs to find out the IM heating and cooling
laws.
IM heat balance equation
Because of difficulties of carrying out the analysis the following
basic assumptions of IM heat balance model are made: an IM is considered
to be an uniform body with infinite thermal conduction and equal point-by-point
temperature. The IM heat capacity and heat transfer factor don’t depend
on IM shaft load. The IM temperature is accepted as the difference between
an actual temperature value and an ambient value and refers to a relative
temperature value
Temperatures of the different motor parts are proportional to each other
and the motor in the whole can be characterized by a mean temperature
T. It’s implied that
the heating process occurs uniformly and the different motor part temperatures
are steady-state.
The mean temperature T is proportional to the quantity of heat Q accumulated
in the motor.
T=Q / C (1)
where C is a heat capacity of the motor.
The heated motor thermal loss are proportional to its temperature.
dQ/dt = - k*T = - k*Q/C (2)
where k is a heat conduction between the motor and ambient air.
It’s supposed that the motor was cold before start.
Following this model the basic heat equation at the motor operation
is
dQ/dt = -k*Q/C + I2R (3)
where I2R is the power released in the motor during the passage of current
I through windings with resistance R.
The solution of the equation at direct current I
Q(t) = Q0 *(1-exp(-t*(k/C))) (4)
The steady–state (dQ/dt=0 ) quantity of heat in the motor is Q0= I2*R*C/k
To the maximum safe motor current I nom correspond the maximum safe
quantity of heat
Q nom = I2nom*R*C/k (5)
and the maximum permissible temperature (relative to environment)
T nom = Q nom /C = I2 nom *R/k (6)
At the motor start on direct current that N times exceeding the maximum
safe I nom
the maximum safe heat quantity period TN is
TN = (ln(N2)-ln(N2-1))/(k/C) (7)
Majotiry of IM heat overload protections is based on the quasithermal
mathematical models of IMs. Continuous I2 calculation allowing for IM
heating and cooling rate with as high as possible measurement digitizing
degree gives a complete view of IM accumulated heat quality which is
considered as dangerous one in the context of allowable insulation heating.
Exceeding of allowable heating for a given insulation class brings about
a so-called accelerated insulation ageing: the mechanical strength decreases,
embrittlement, fractures, cracks and occur causing the insulation electric
strength decrease and disruption.
Insulation resistance decrease. While IMs are in use
their insulation is inevitably «ageing».
Principal causes of the ageing are heating of windings through operating
and starting currents, short-circuit currents, overload currents and
external source heat; through dynamic forces resulting from lead interaction
and through switching surges. The insulation condition is influenced
by ambient conditions such as air temperature and humidity, air pollution
and dust content.
The degree of operational safety of electrical installation is determined
by the insulation condition. An IM is allowed to be used only if its
insulation resistance to frame is not less than
0,5 Mom. The insulation disruption probability increases by an order
of magnitude if the
insulation resistance is twice less than the allowable one.
The insulation resistance drop increases the probability of such IM
fault as the stator winding breakdown to the frame (ground fault) which
is dangerous not only for the IM itself but also for the service staff.
Short-circuit currents that 10-100 times exceed the nominal currents
start to run through the supply line and the electric installation frame
can be found under high voltage that is endangering life. It’s very
significant to carry out continuous monitoring of the stator winding
insulation resistance during the IM use because dielectric insulation
properties measured before the IM cut-in can suddenly change under influence
of electric voltage and temperature. For this purpose the ground leakage
current is measured by the differential current transformer that responds
to the occurring of the difference current that exceeds the user-specified
setting.
Fault condition protection methods. In order to provide
IM protection against
faulty conditions the different kinds of relay protection – thermal,
current, temperature, filter and combined ones – have been come into
use since the middle of the last century.
For the years of IM service experience it has been shown that most
existing systems don’t provide the fail-safe operation of IMs. Thus,
for instance, thermal relays are designed for long-term overload that
is 25-30% of the nominal one. But more often they trip at one phase
loss under the load that is 60% of the nominal one. Under a lesser load
the relay doesn’t trip and an IM keeps operating from two phases that
brings about the winding insulation overheating and the IM failure.
The correct choice of the protection device is an important factor for
the fail-safe operation of IMs.
Protection devices against IM faulty conditions come in several types:
A) thermal protection devices: thermal relays, tripping devices;
B) current-dependent protection devices: fuses, circuit-breakers;
C) heat-sensitive protection devices: thermistors, thermostats;
D) protection from mains faults: phase voltage & phase monitoring
relays, mains monitors;
F) maximum current protection devices, electronic current relays;
G) combined protection devices.
In the second chapter of this article we are trying to give a detailed
description of principles of operation, strengths and weaknesses of
the existing protections as well as to discuss attempts to create universal
protection devices for IMs.
Sorkind Michail, chief manager of NOVATEK-ELECTRO LTD (St. Petersburg)